3KM5530-1EB01
SW.DISCON. W.F.+DR 3P 250A/SZ.2

From SIEMENS

SWITCH DISCONNECTOR FUSE NEW DESIGN IU=250A, UE=690V, 3-POLE FOR LV HRC FUSE SIZE 1 AND 2 W. DOOR COUPL. ROTARY OP. MECH. 8UC6 HANDLE BLACK W. ISOLATING PLUG CONN. FOR MCC
Model
Product brand nameSENTRON
versionComplete version with rotary operating mechanism
Design typeplug connector on the top
Design of the operating mechanismmanual operating mechanism
Type of the driving mechanism / motor driveNo
Number of poles3
Size of disconnecting link2 and 1
Fuse systemLV HRC fuse
Insulation voltage / rated value1 000 V
Surge voltage resistance / rated value8 000 V
Protection class
Protection class IPIP00
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole11 W
Electricity
Operating current / at AC-21 / rated value250 A
Continuous current / rated value250 A
Let-through current / I2 t / maximum permissible / in utilization category / AC-22 B / at 400 V1 000 000 A²·s
Main circuit
Number of poles / for main current circuit3
Operating power
at AC-23 A / at 400 V / at 50/60 Hz / rated value132 000 W
at AC-23 A / at 500 V / at 50/60 Hz / rated value132 000 W
at AC-23 A / at 690 V / at 50/60 Hz / rated value185 000 W
Operating voltage
at AC / at 50/60 Hz / rated value690 V
at DC / rated value440 V
Rated current Ie / maximum / in utilization category
AC-21 A / at 400 V250 A
AC-21 A / at 500 V250 A
AC-21 B / at 400 V250 A
AC-21 B / at 500 V250 A
AC-22 A / at 400 V250 A
AC-22 A / at 500 V250 A
AC-22 B / at 400 V250 A
AC-22 B / at 500 V250 A
Auxiliary circuit
Number of CO contacts / for auxiliary contacts0
Number of NC contacts / for auxiliary contacts0
Number of NO contacts / for auxiliary contacts0
Suitability for use
EMERGENCY OFF switchNo
safety switchYes
Product feature / interlockYes
Short circuit
Conditional rated short-circuit current / in utilization category
AC-21 A / at 400 V100 kA
AC-21 A / at 500 V100 kA
AC-21 B / at 400 V100 kA
AC-21 B / at 500 V100 kA
AC-22 A / at 400 V100 kA
AC-22 A / at 500 V100 kA
AC-22 B / at 400 V100 kA
AC-22 B / at 500 V100 kA
Connections
Connectable conductor cross-section
for main contacts
— stranded / maximum150 mm²
Type of connection, main circuitflat connector bottom connection, M10
Type of electrical connection
for main current circuitflat connector
Mechanical Design
Height160 mm
Width247 mm
Depth279 mm
Type of mountingplug-in version
Mounting positionany
Mounting typeclip-on
Mounting type
front mounting with 4-hole attachmentNo
front mounting with central attachmentNo
rail mountingYes
Environmental conditions
Ambient temperature
during operation / minimum-25 °C
during operation / maximum55 °C
during storage / minimum-50 °C
during storage / maximum80 °C

External links