3VA1112-5MH32-0AA0
MCCB_IEC_FS160_125A_3P_55KA_TM_ AM

From SIEMENS

circuit breaker 3VA1 IEC frame 160 breaking capacity class M Icu=55kA @ 415V 3-pole, starter protection TM120M, AM, In=125A without overload protection short-circuit protection Ii=7...16 x In nut keeper kit
Model
Product brand nameSENTRON
Product designationMolded case circuit breaker
Product versionStarter protection
Design of the overcurrent releaseTM120M
Protective function of the overcurrent releaseI
Number of poles3
General technical data
Rated insulation voltage Ui800 V
Max. rated operational voltage Ue with AC 50/60Hz690 V
Power loss [W] / maximum28.1 W
Active power loss / for rated value of the current / at AC / in hot operating state / per pole9.37 W
Latching - endurance20 000
Electrical endurance (switching cycles) / at AC-1 / at 380/415 V 50/60 Hz8 000
Electrical endurance (switching cycles) / at AC-1 / at 690 V 50/60 Hz8 000
Neutral conductors / upgradeable/retrofittableNo
Ground fault monitoring versionWithout
Product function
communication functionNo
Phase failure detectionNo
other measurement functionNo
Net weight0.9 kg
Electricity
Max. rated operational voltage of the size of the circuit-breaker160 A
Rated continuous current Iu125 A
Operating current
at 40 °C125 A
at 45 °C125 A
at 50 °C125 A
at 55 °C122 A
at 60 °C120 A
at 65 °C117 A
at 70 °C114 A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breakerM
Maximum short-circuit current breaking capacity (Icu)
at 240 V85 kA
at 415 V55 kA
at 440 V36 kA
at 500 V5 kA
at 690 V5 kA
Operational short-circuit current breaking capacity (Ics)
at 240 V85 kA
at 415 V55 kA
at 440 V36 kA
at 500 V5 kA
at 690 V5 kA
Short-circuit current making capacity (Icm)
at 240 V187 kA
at 415 V121 kA
at 440 V76 kA
at 500 V7.5 kA
at 690 V7.5 kA
Adjustable parameters
Short-term delayed / tripping switchable / I2t=ON/OFFNo
Adjustable response value current / li min.875 A
Adjustable response value current / li max.2 000 A
Ground fault protection / tripping switchable / I2t=ON/OFFNo
Mechanical Design
Height [in]5.1 in
Height130 mm
Width [in]3 in
Width76.2 mm
Depth [in]2.8 in
Depth70 mm
Connections
Arrangement of electrical connectors / for main current circuitFront terminal
Type of electrical connection / for main current circuitlug terminal
Type of connectable conductor cross-section, connection screw, width x thickness , min.12 x 1
Type of connectable conductor cross-section, connection screw, width x thickness , max.17 x 6.5
Auxiliary circuit
Number of CO contacts / for auxiliary contacts0
Accessories
Product extension / optional / motor driveYes
Environmental conditions
Protection class IP / on the frontIP40
Ambient temperature
during operation / minimum-25 °C
during operation / maximum70 °C
during storage / minimum-40 °C
during storage / maximum80 °C

External links